Calculators / Vents and chimneys
Fireplace insert size, hearth and chimney planner
Put in your fireplace opening, what you want to burn, the mantel and hearth, and how the chimney sits on the roof. You get which inserts the makers say fit, the IRC’s hearth extension and mantel clearance, the 3-2-10 chimney check with a side view, and each maker’s own clearances.
Updated · How we check our numbers
Fits, and the code checks pass
Fits 3 wood inserts
Your 36 x 29 in opening takes the Napoleon S25i (31 in wide minimum), Regency CI2600 (28 13/16 in wide minimum) and Lopi Answer NexGen-Hybrid (23 7/8 in wide minimum), but your mantel is under Napoleon and Regency’s own clearance. Your mantel at 12 in above the opening sticking out 6 in needs 12 in per IRC R1001.11. The chimney at 4 ft above the roof meets the 3-2-10 rule’s 4 ft.
- Opening
- 36 x 29 in20 in deep, 7.3 sq ft
- Wood inserts that fit
- 3 of 3
- Hearth the IRC asks
- 20 in front12 in each side
- Chimney needs
- 4 ftabove the roof
Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.
What the liner costsA stainless liner, priced by the foot, guide by guide
A TV above the fireplaceWhat size, and how far you look up to it
Opening area: 36 × 29 ÷ 144 = 7.3 sq ft (6 or more: 20 in front, 12 in each side)
Mantel: 6 in out × 8 = 48 in; at least 6 in, and past 12 in the rule stops → 12 in
Roof within 10 ft: 6/12 × 4 ft = 2 ft → highest 2 ft
Chimney: the larger of 3 ft and 2 ft + 2 ft = 4 ft
Roof at 6 in 12, the ridge 4 ft from the chimney. Dashed: the 10 ft the rule looks across, and the height it asks for (2 ft over the highest part within 10 ft, 2 ft up).
Which wood inserts fit your opening
36 x 29 in, 20 in deep- Napoleon S25iNeeds 31 in wide, 23 1/2 in high, 15 1/2 in deep, 29 in at the back. Full height listed HT chimney liner.Mantel too low
Fits the opening. Napoleon: 53 1/2 in up from the hearth (yours: 41 in). Hearth: 16 in in front and 8 in each side, from the front of the insert.
- Regency CI2600Needs 28 13/16 in wide, 21 3/4 in high, 19 in deep. 5.5 or 6 in stainless liner, top to bottom.Mantel too low
Fits the opening. Regency: 21 5/8 in from the top of the insert’s door, mantel 10 in deep at most. Hearth: 16 in in front and 8 in each side, from the fuel door.
- Lopi Answer NexGen-HybridNeeds 23 7/8 in wide, 21 in high, 14 1/2 in deep, 23 7/8 in at the back. 6 in full-height stainless liner; chimney 15 to 33 ft from the insert’s base.Fits
Fits the opening. Lopi: 35 1/2 in up from the hearth (yours: 41 in), mantel 12 in deep at most. Hearth: 16 in in front and 6 in each side, from the front of the insert (18 in from the opening).
Each maker’s minimum fireplace opening, from its own manual or spec sheet. Measure again before you order: minimums change with the faceplate.
Your fireplace against the IRC
- Hearth extension in front (IRC R1001.10)7.3 sq ft opening: 20 in in front (6 sq ft or larger)20 in: enough
- Hearth extension past each side (IRC R1001.10)12 in beyond each side of the opening12 in: enough
- Combustible mantel (IRC R1001.11)Sticking out 6 in: within 12 in it could stick out only 1/8 in per inch of distance, so it needs 12 in12 in: clear
- Firebox depth (IRC R1001.6)20 in for a masonry fireplace; a Rumford 12 in and a third of the opening’s width20 in: deep enough
- Chimney: 3 ft above the roof (IRC R1003.9)Above the highest point where it passes through the roof4 ft: enough
- Chimney: 2 ft over anything within 10 ft (IRC R1003.9)The highest part of the house within 10 ft is 2 ft above where the chimney leaves the roof, so 4 ftClears it
The IRC as Seattle’s building department prints it (2021). Your city or county adopts its own edition and may amend it.
Width and height across the front of the opening; depth from the front edge to the back wall at the floor; the back width where the firebox narrows. Makers measure their own way (Mendota also gives a depth to the taper; Regency’s minimums change with the faceplate), so check the manual for the model before you buy.
The IRC’s R1001.11 is for a masonry fireplace on its own: nothing combustible within 6 in of the opening, and within 12 in a mantel can stick out 1/8 in for each inch it sits above. Once an insert goes in, its maker’s clearance applies too, and it’s usually bigger: Regency’s CI2600 wants 21 5/8 in from the top of its door. Raise the mantel, swap it for a non-combustible one where the maker allows, or pick a smaller insert.
Every wood insert here needs a full-height stainless liner from the insert to the top of the chimney: Regency says 5.5 or 6 in, Lopi 6 in, Napoleon a listed HT liner. CSIA recommends a Level 2 inspection before relining or adding an appliance.
How we work it out
Which inserts fit
Every insert maker prints a minimum fireplace opening: front width, height, depth and usually the width at the back, where the firebox narrows. Regency's CI2600 wood insert says: “Your fireplace opening requires the following minimum sizes: Height: 21-3/4" Width: 28-13/16" Depth: 19".” We compare your opening with each one, from the makers' own manuals and spec sheets: Regency, Lopi, Napoleon and Mendota for inserts, Astria for vent-free log sets. Kozy Heat's site and napoleon.com refused our reader, so Napoleon's figures come from its manual as a parts site hosts it.
Hearth extension
IRC R1001.10: “Hearth extensions shall extend not less than 16 inches (406 mm) in front of and not less than 8 inches (203 mm) beyond each side of the fireplace opening. Where the fireplace opening is 6 square feet (0.6 m2) or larger, the hearth extension shall extend not less than 20 inches (508 mm) in front of and not less than 12 inches (305 mm) beyond each side.” An insert brings its own rule, measured from its door or front, which sits forward of the opening: Regency, Lopi and Napoleon each ask 16 in in front in the US. A factory-built fireplace follows its listing instead (R1004.2).
opening area = width × height ÷ 144; 6 sq ft or more → 20 in front, 12 in each side
Mantel clearance
IRC R1001.11 lets a combustible mantel sit on a masonry fireplace's front “providing such combustible materials are not placed within 6 inches (152 mm) of a fireplace opening. Combustible material within 12 inches (306 mm) of the fireplace opening shall not project more than 1/8 inch (3 mm) for each 1-inch (25 mm) distance from such an opening.” So a mantel sticking out 6 in has to be 12 in up. An insert's maker usually asks more: Regency's CI2600 wants 21 5/8 in from the top of its door and a mantel no deeper than 10 in.
mantel height = 8 × how far it sticks out, at least 6 in; at 12 in or more the rule stops
Chimney height: the 3-2-10 rule
IRC R1003.9: “Chimneys shall extend not less than 2 feet (610 mm) higher than any portion of a building within 10 feet (3048 mm), but shall be not less than 3 feet (914 mm) above the highest point where the chimney passes through the roof.” We work out the highest roof within 10 ft from the pitch and the distance to the ridge, or a taller wall or dormer if you give one.
chimney height = the larger of 3 ft and (highest part within 10 ft + 2 ft)
We quote the IRC as Seattle's building department prints it in its 2021 Residential Code; none of these sections carries a Washington amendment. Your city adopts its own edition. Read November 9, 2026.
Vent-free gas logs
Astria's instructions say the logs “shall not be installed in a bedroom or bathroom,” the room must hold 1 cu ft for every 20 Btu/Hr, and “State or local codes may only allow operation of this appliance in a vented configuration.” In California, Gilroy's building division quotes the Green Building Code: “Any installed gas fireplace shall be a direct vent sealed-combustion type (i.e., No Gas Logs Allowed).” The state statute's site refused our reader.
Next: the liner or the insert priced on the chimney repair cost page, and a TV above the mantel on the TV size calculator, which works out the size and how far you look up.
Where the numbers come from
- Seattle Residential Code 2021, Chapter 10 (IRC R1001 to R1004), SDCI
- Regency CI2600 wood insert spec sheet
- Regency CI2600/HI400 owners and installation manual (919-551c)
- Regency Gi27LE gas insert spec sheet
- Lopi Answer NexGen-Hybrid manual (Travis Industries 100-01568)
- Napoleon S25i installation manual (W415-2902)
- Mendota FV33i gas insert: minimum fireplace dimensions
- Mendota FV44i gas insert: minimum fireplace dimensions
- Astria Magniflame vent-free gas log heater instructions (900741-00 Rev. E)
- City of Gilroy Building Division: residential fireplace requirements (2025)
- CSIA: Level 2 inspection, masonry chimney (SOP)
Guides
Fireplace and chimney
Upkeep
More calculators
- Dryer vent lengthIs my dryer vent too long for the code and my dryer, and what does cleaning cost?
- Chimney repair costWhat does a chimney sweep, inspection, cap, crown or liner cost?
- Well water testWhat do my well water test results mean?
- Water softener sizeWhat size water softener do I need?
- RO waste waterHow much water does my reverse osmosis system waste?
- Gutter sizeDo I need 5 or 6 inch gutters, and how many downspouts?
- Bathroom layoutDoes my bathroom layout meet code clearances?
- Bidet plannerBidet seat, attachment or smart toilet: which fits my toilet?