What size AC do I need?
Whole-house AC size comes from a Manual J load calculation. Put in your house to see what it should use, then add the contractor’s numbers to check the quote.
Updated · How we check our numbers
Needs a Manual J
Ask for a Manual J
The right size for your 2,000 sq ft house comes from a Manual J load calculation, not square feet per ton. The International Residential Code requires it. Here’s what it should use; put the contractor’s numbers in to check a quote.
- Floor area
- 2,000 sq ft
- Occupants
- 4bedrooms + 1
- Indoor
- 75 °Fcooling design
- Old unit
- 4 tons
Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.
What it costsAC installed price by size, NREL data
Read a quote in tonsBTU to tons converter
What goes into your Manual J
ACCA verification points- Location and outdoor design temperatureFrom Manual J Tables 1A or 1B for your townCheck
The 1% summer dry-bulb for cooling, the 99% winter one for heating. Ask why if they differ from the tables.
- Indoor design temperature75 °F cooling, 70 °F heatingCheck
ACCA’s defaults unless a code or regulation says otherwise.
- Conditioned floor area2,000 sq ft (yours)Check
As built or on the plan.
- Occupants4 (bedrooms + 1)Check
ACCA counts bedrooms plus one.
- Windows, orientation and shadingEach window’s size, type and the way it faces; eave overhangsCheck
Fenestration is one of the loads Manual J adds up, and ACCA wants overhangs and shading included.
- Walls, ceilings, floors and skylightsInsulation levels and areasCheck
From the house or the plan, not a worst case.
- Air leakage and ventilationA blower door number if you have oneCheck
A “very loose” guess on a tight house inflates the load.
- DuctsIn the attic (yours)Check
Ducts outside the conditioned space are part of the system load Manual J adds.
From ACCA’s checklist for code officials (ICC, 2018). Ask for the report.
4 tons (48,000 Btu/h). Matching it isn’t a sizing method: the code asks for Manual J, and insulation, windows or the old unit’s own sizing may have changed.
Ask the contractor for the Manual J load report and the Manual S equipment selection. The code requires equipment “sizing per ACCA Manual S based on ACCA Manual J” (IRC M1401.3). Manual S “sets upper and lower limits for equipment total capacity”, and the capacity it checks should be the maker’s performance data at your design conditions, not the AHRI rating.
ACCA doesn’t support: changed design temperatures, designing for a worst-case house, more occupants than bedrooms plus one, duct loads for ducts inside the house, leaving out overhangs and shading, padded internal loads, a safety factor, or rounding up to the next size.
ENERGY STAR: “a system that’s too large will not keep your home comfortable because of frequent ‘on/off’ cycling.”
ENERGY STAR’s square-foot chart covers single rooms; the mini-split calculator uses it.
How we work it out
size = Manual J cooling load for your house → Manual S picks equipment within its limits · tons = Btu/h ÷ 12,000
We looked for a published quick estimate for a whole house and didn't find one we could stand behind. ENERGY STAR's square-foot chart is for room air conditioners, and ACCA describes Manual J and Manual S without a shortcut. The International Residential Code (M1401.3) requires equipment sized by Manual S from loads worked out by Manual J, so that's what this page is built on. No square-feet-per-ton figure here.
What goes into a Manual J
The checklist for code officials presented at the 2018 ICC Annual Conference: your town's outdoor design temperatures from Manual J Tables 1A or 1B (the 1% summer and 99% winter conditions), 75 °F inside for cooling and 70 °F for heating, the house's real orientation and floor area, occupants equal to bedrooms plus one, overhangs and shading, skylights, and sensible plus latent heat adding up to the total. The loads it adds are windows and doors, walls, ceilings and floors, air leakage, ventilation, people and appliances, and the ducts and blower.
When to insist on one
Always, for a new system: it's the code. It matters most when the quote just matches the old unit, when it's sized by square feet, or when the house has changed since the last unit went in. Ask for the report and check it for the padding ACCA doesn't support: changed design temperatures, a worst-case house, extra occupants, duct loads for ducts inside the house, missing overhangs, a safety factor, or rounding up to the next size.
Checking the quote
Ask the contractor for two documents: the Manual J load report and the Manual S equipment selection. ACCA's overview for code officials says Manual S “Sets upper and lower limits for equipment total capacity”, and warns against using “AHRI rated capacities instead of OEM engineering performance data”, rounding up to the next size, or equipment outside the sizing limits. Those limits vary by edition and equipment type, so we show the unit as a percentage of the load rather than judge it; the Manual S selection should say which limit it used. ENERGY STAR on why bigger isn't better: “a system that's too large will not keep your home comfortable because of frequent ‘on/off’ cycling.”
Where the numbers come from
Guides
Heating and cooling
More calculators
- Furnace sizeWhat size furnace do I need for my heat loss and design temperature?
- Heat pump sizeWhich heat pumps cover my house at my design temperature, and how much backup heat?
- Mini-split sizingWhat size mini-split heats and cools my garage or room?
- BTU to tonsHow many tons is my BTU number, and which mini-split is that?
- SEER2 savingsHow much will a higher SEER2 AC or heat pump save?
- AC unit costWhat does a new AC unit, heat pump or furnace cost installed?
- Dehumidifier sizingWhat capacity keeps my garage or basement dry?
- Air filter sizeWhat size furnace or AC filter, which MERV, and how often to change it?