Calculators / HVAC sizing

What size AC do I need?

Whole-house AC size comes from a Manual J load calculation. Put in your house to see what it should use, then add the contractor’s numbers to check the quote.

Updated · How we check our numbers

These are example numbers. Put in yours.

Your house

sq ft
Where the ducts run
tons

On the outdoor unit’s model number: 24 = 2 tons, 36 = 3, 48 = 4, 60 = 5.

The contractor’s numbers

Btu/h

On the Manual J report. Leave blank if you don’t have one yet.

Btu/h

The maker’s capacity at your design conditions, from the Manual S sheet.

Needs a Manual J

Ask for a Manual J

The right size for your 2,000 sq ft house comes from a Manual J load calculation, not square feet per ton. The International Residential Code requires it. Here’s what it should use; put the contractor’s numbers in to check a quote.

Floor area
2,000 sq ft
Occupants
4bedrooms + 1
Indoor
75 °Fcooling design
Old unit
4 tons

Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.

What it costsAC installed price by size, NREL data

Read a quote in tonsBTU to tons converter

What goes into your Manual J

ACCA verification points
  • Location and outdoor design temperatureFrom Manual J Tables 1A or 1B for your town
    Check

    The 1% summer dry-bulb for cooling, the 99% winter one for heating. Ask why if they differ from the tables.

  • Indoor design temperature75 °F cooling, 70 °F heating
    Check

    ACCA’s defaults unless a code or regulation says otherwise.

  • Conditioned floor area2,000 sq ft (yours)
    Check

    As built or on the plan.

  • Occupants4 (bedrooms + 1)
    Check

    ACCA counts bedrooms plus one.

  • Windows, orientation and shadingEach window’s size, type and the way it faces; eave overhangs
    Check

    Fenestration is one of the loads Manual J adds up, and ACCA wants overhangs and shading included.

  • Walls, ceilings, floors and skylightsInsulation levels and areas
    Check

    From the house or the plan, not a worst case.

  • Air leakage and ventilationA blower door number if you have one
    Check

    A “very loose” guess on a tight house inflates the load.

  • DuctsIn the attic (yours)
    Check

    Ducts outside the conditioned space are part of the system load Manual J adds.

From ACCA’s checklist for code officials (ICC, 2018). Ask for the report.

Your old unit

4 tons (48,000 Btu/h). Matching it isn’t a sizing method: the code asks for Manual J, and insulation, windows or the old unit’s own sizing may have changed.

Ask for both reports

Ask the contractor for the Manual J load report and the Manual S equipment selection. The code requires equipment “sizing per ACCA Manual S based on ACCA Manual J” (IRC M1401.3). Manual S “sets upper and lower limits for equipment total capacity”, and the capacity it checks should be the maker’s performance data at your design conditions, not the AHRI rating.

Push back on

ACCA doesn’t support: changed design temperatures, designing for a worst-case house, more occupants than bedrooms plus one, duct loads for ducts inside the house, leaving out overhangs and shading, padded internal loads, a safety factor, or rounding up to the next size.

Why bigger isn’t better

ENERGY STAR: “a system that’s too large will not keep your home comfortable because of frequent ‘on/off’ cycling.”

Just one room or a garage?

ENERGY STAR’s square-foot chart covers single rooms; the mini-split calculator uses it.

How we work it out

size = Manual J cooling load for your house → Manual S picks equipment within its limits · tons = Btu/h ÷ 12,000

We looked for a published quick estimate for a whole house and didn't find one we could stand behind. ENERGY STAR's square-foot chart is for room air conditioners, and ACCA describes Manual J and Manual S without a shortcut. The International Residential Code (M1401.3) requires equipment sized by Manual S from loads worked out by Manual J, so that's what this page is built on. No square-feet-per-ton figure here.

What goes into a Manual J

The checklist for code officials presented at the 2018 ICC Annual Conference: your town's outdoor design temperatures from Manual J Tables 1A or 1B (the 1% summer and 99% winter conditions), 75 °F inside for cooling and 70 °F for heating, the house's real orientation and floor area, occupants equal to bedrooms plus one, overhangs and shading, skylights, and sensible plus latent heat adding up to the total. The loads it adds are windows and doors, walls, ceilings and floors, air leakage, ventilation, people and appliances, and the ducts and blower.

When to insist on one

Always, for a new system: it's the code. It matters most when the quote just matches the old unit, when it's sized by square feet, or when the house has changed since the last unit went in. Ask for the report and check it for the padding ACCA doesn't support: changed design temperatures, a worst-case house, extra occupants, duct loads for ducts inside the house, missing overhangs, a safety factor, or rounding up to the next size.

Checking the quote

Ask the contractor for two documents: the Manual J load report and the Manual S equipment selection. ACCA's overview for code officials says Manual S “Sets upper and lower limits for equipment total capacity”, and warns against using “AHRI rated capacities instead of OEM engineering performance data”, rounding up to the next size, or equipment outside the sizing limits. Those limits vary by edition and equipment type, so we show the unit as a percentage of the load rather than judge it; the Manual S selection should say which limit it used. ENERGY STAR on why bigger isn't better: “a system that's too large will not keep your home comfortable because of frequent ‘on/off’ cycling.”