Calculators / Water heaters

Can your panel handle an electric water heater?

Pick the water heater and tell us about your panel and the big things in the house. You get the breakers and wire it needs and whether your service has room.

Updated · How we check our numbers

These are example numbers. Put in yours.

The water heater

Electric water heater

Your panel and house

Main breaker

The big breaker at the top of the panel. The number is on the handle.

sq ft

Finished, lived-in floor space.

Water heater now

The one you're replacing. We take it out of the load.

Clothes dryer
Heat and AC
EV charger
kW

Pool pump, well pump, sauna, shop heater. Add up the nameplates. Leave blank if none.

Your panel can take it

Three 40 A double-pole, 3 runs of 8 AWG

The tankless, 27 kw draws 113 A. With it, your house load comes to about 115 A of your 200 A panel.

Draws
113 A27.0 kW at 240 V
Breakers
3 × 40 A double-pole
House load with it
115 Aof 200 A
Left over
85 A

Estimate for planning only, not professional advice. Check the manufacturer’s instructions, your local code and a licensed professional before you buy, build or install. Use at your own risk. Terms.

Running costHeat pump vs electric vs gas, a year

Tankless, 27 kW: 27.0 kW ÷ 240 V = 112.5 A; Rheem RTEX-27: three 40 A double-pole, 3 runs of 8 AWG

lights and plugs = 1800 sq ft × 3 VA = 5.4 kVA

house loads = 5.4 kVA + kitchen and laundry circuits 4.5 kVA + appliances 7.5 kVA + tankless, 27 kw 27 kVA = 44.4 kVA

counted = 8 kVA + (44.4 kVA − 8 kVA) × 40% = 22.6 kVA

with heat and AC at 100% = 22.6 kVA + 5 kVA = 27.6 kVA

load = 27.6 kVA ÷ 240 V = 115 A of your 200 A panel

before = 70 A; with it = 115 A

Every type on your panel

220.83 load check
  • Electric tank, 4,500 W18.8 A; one 30 A double-pole (Bradford White allows 25 A), 10 AWG
    123 A left
  • Heat pump water heater (240 V)18.8 A; one 30 A double-pole, 10 AWG
    123 A left
  • Tankless, 13 kW (point of use)54 A; one 60 A double-pole, 6 AWG
    109 A left
  • Tankless, 18 kW75 A; two 40 A double-pole, 2 runs of 8 AWG
    100 A left
  • Tankless, 24 kW100 A; three 40 A double-pole, 3 runs of 8 AWG
    90 A left
  • Tankless, 27 kW113 A; three 40 A double-pole, 3 runs of 8 AWG
    85 A left
  • EcoSmart ECO 27113 A; three 40 A double-pole, 3 runs of 8 AWG
    85 A left
  • Stiebel Eltron Tempra 36 Plus150 A; three 50 A double-pole, 3 runs of 8/2 AWG
    70 A left
  • Tankless, 36 kW150 A; four 40 A double-pole, 4 runs of 8 AWG
    70 A left
Panel space

Count your empty spaces: three 40 A double-pole take 6 breaker slots.

The wire from the street

113 A is a big share of any house's service. Your utility's service wire and meter have limits too; ask an electrician before you buy.

Permit

Most towns want a permit for a new 240 V circuit. This is a planning check, not a load calculation stamped by an electrician.

How we work it out

The circuit. A standard electric tank and a heat pump water heater both have 4,500 W elements on 240 V. Rheem and A.O. Smith list a 30 A double-pole breaker; Bradford White lists 25 A with 10 AWG wire. Electric tankless units are a different scale: Rheem's 27 kW model draws 113 A and needs three 40 A double-pole breakers, each with its own 8 AWG run.

amps = watts ÷ 240 V

The panel. We add the heater to your house with the National Electrical Code's existing-dwelling method (220.83, 120.83 in the 2026 edition), the same check our hot tub and EV charger calculators use: 3 VA per sq ft for lights and plugs, the kitchen and laundry circuits, and every fixed appliance at nameplate, with the first 8 kVA counted in full and the rest at 40%. Heat and AC go on top at 100%. The water heater you have now comes out of the total.

house amps = counted load ÷ 240 V, compared with your main breaker

Under 10 A to spare, we call it tight. This is a planning check. An electrician's load calculation and the permit settle it.